Fire damper inspection and testing

We find, inspect and drop-test every fire damper in your building, and give you a damper-by-damper record your fire inspector can rely on.

Fire separation Fusible link Fire damper Access door Closed Front view

When you need it

  • A new building or renovation needs its dampers tested before occupancy.
  • The annual fire inspection is due, or an inspector has asked for damper records.
  • The dampers have never been tested, or nobody knows where they all are.
  • Ductwork or walls around the dampers have been modified.

What we do

  1. Locate

    We work from the drawings and the ceiling space to find every damper, and note any without access doors.

  2. Inspect

    We check that each damper is installed, unobstructed and undamaged, and that its fusible link is in place.

  3. Drop-test

    We release the link or trigger the actuator, confirm the damper closes fully and latches, then reset it.

  4. Record

    Each damper gets a location tag and a line in the inventory with its result and any repair needed.

What you receive

  • A damper inventory with location and access notes
  • A pass or fail result for each damper
  • A deficiency list: missing access doors, failed closures, damaged links
  • Records ready for your fire inspector

Questions

How often do fire dampers need to be checked?

The National Fire Code of Canada requires fire dampers to be inspected at least every 12 months and tested in accordance with NFPA 80. NFPA 80 calls for testing after installation, again one year later, and then every four years, or every six years in hospitals. Your provincial code and fire department may set their own requirements.

What if a damper can’t be reached?

We record it as inaccessible, with its location, so an access door can be installed. A damper that can’t be tested is a gap in the building’s fire protection.

What’s the difference between a fire damper and a smoke damper?

A fire damper closes when heat melts its fusible link, stopping fire spreading through a duct. A smoke damper is closed by the fire alarm or controls to stop smoke moving through the building. Many buildings have combination dampers that do both.