Solar energy can serve a building's HVAC and hot water systems in two broad ways. Solar thermal systems capture sunlight as heat, either in water or glycol for domestic hot water and space heating, or in air for preheating ventilation. Photovoltaic (PV) systems convert sunlight to electricity, which can then run heat pumps, fans and pumps. As buildings electrify, PV has become the more common choice, but solar thermal still has strong applications where heat is needed in the right quantity at the right time.
Much of southern Canada has good solar resource, with the Prairies among the sunniest regions in the country. The challenge is not the amount of sunlight over a year but its timing: most solar energy arrives in summer, while heating loads peak in winter. Good integration accounts for that mismatch.
Comparing the options
| Technology | Output | Best matches | Main limitations |
|---|---|---|---|
| Glazed flat plate or evacuated tube collectors | Hot water or glycol | Domestic hot water, pools, process heat | Overheating in summer if loads are small; freeze protection |
| Unglazed collectors | Warm water | Outdoor pools, low-temperature preheat | Low temperature output, mostly seasonal |
| Transpired solar air collectors | Preheated outdoor air | Ventilation preheat for buildings with large outdoor air flows | Only useful when ventilation runs during daylight |
| Photovoltaic (PV) | Electricity | Heat pumps, fans, pumps, plug loads, export to grid | Output depends on grid interconnection rules and storage |
| PV-thermal (PVT) | Electricity and low-grade heat | Heat pump source, pool heating | More complex, smaller market |
Solar thermal for hot water
Domestic hot water is the classic solar thermal load, because demand exists year round. Hotels, multi-unit residential buildings, long-term care homes, fitness centres and laundries are good candidates.
A typical commercial system includes collectors, a glycol loop with a pump station, a heat exchanger, solar storage tanks and a conventional or heat pump water heater as backup. Design points:
- Size to the summer load, not the annual load, to avoid overheating and stagnation when demand drops.
- Freeze protection: glycol loops or drainback systems are required in Canadian climates.
- Stagnation management: when storage is full, collectors can reach very high temperatures. Systems need expansion capacity, heat dumps or drainback design.
- Preheat arrangement: solar storage usually feeds the backup heater, so the backup only adds the remaining temperature lift.
- Legionella control: storage and distribution temperatures must still meet public health requirements.
CSA standards cover solar collectors and packaged solar water heating systems, and installations must comply with plumbing codes adopted in the province.
Solar air heating
Transpired solar collectors are perforated dark metal panels mounted on a south-facing wall with an air gap behind. The ventilation fan draws outdoor air through the perforations, where it picks up heat from the sun-warmed surface before entering the air handler intake. These systems were developed in Canada and suit buildings with large daytime ventilation loads, such as warehouses, factories, schools and aircraft hangars.
They work best when the collector wall is near the air handler intake and ventilation runs during daylight hours in the heating season. In summer, a bypass damper draws air directly from outdoors. Collector placement must respect intake separation requirements from exhaust and other contaminant sources; see outdoor air intake placement and design.
PV and heat pumps
PV paired with heat pumps is now the most common solar strategy for net-zero ready buildings. PV electricity can supply heat pumps, fans, pumps and other loads. Because production peaks in summer and heating peaks in winter, annual net-zero usually relies on exporting summer surplus to the grid and importing in winter.
Integration considerations:
- Interconnection and net metering: rules differ by province and utility, including limits on system size, credit for exported energy and approval processes. Alberta's micro-generation rules, BC Hydro's net metering program and Ontario's net metering regulation each work differently.
- Electrical code: PV installations follow the Canadian Electrical Code, Part I (CSA C22.1), including the section on renewable energy systems, plus utility interconnection requirements.
- Roof planning: HVAC equipment competes with PV for roof area. Consolidating rooftop equipment, using ground-level or mechanical penthouse locations, and designing structure for PV loads preserves roof space.
- Snow: panels at steeper tilt shed snow better; winter output is reduced on flat arrays.
- Self-consumption: shifting loads into sunny hours, such as pre-cooling, heating domestic hot water with heat pumps during the day, or charging thermal storage, increases on-site use of PV output.
Solar with thermal storage
Thermal storage can help bridge the timing mismatch. Short-term storage in hot water tanks shifts solar heat to evening loads. Some systems use PV electricity to run heat pumps into thermal storage during the day. Seasonal storage, such as borehole thermal storage that stores summer solar heat for winter use, has been demonstrated in Canada but requires community scale and careful design.
Controls
Solar systems need controls that coordinate with the HVAC system:
- Solar thermal pump control based on collector and tank temperature difference.
- High limit and stagnation protection.
- Damper control on transpired collectors with summer bypass.
- Load shifting sequences that use PV output for heat pumps or storage.
- Metering of solar thermal output and PV generation, so performance is visible.
Without monitoring, failed solar thermal pumps or glycol degradation can go unnoticed for years while backup heaters quietly take over.
Economics
Solar economics depend on the energy displaced, its price, available incentives and interconnection rules. Solar thermal replacing gas water heating competes with low gas prices; replacing electric resistance water heating it competes better. PV economics have improved substantially as module prices have fallen. A life-cycle cost analysis that includes maintenance and component replacement, such as inverters and pumps, gives a fair comparison.
Frequently asked questions
Should I choose solar thermal or PV?
For most buildings electrifying with heat pumps, PV is simpler and more flexible. Solar thermal makes sense where there is a large, steady hot water load, or for ventilation preheat with transpired collectors.
Does snow make solar ineffective in Canada?
Snow reduces winter output, but most annual production occurs from spring to fall. Tilted arrays and wall-mounted collectors shed snow faster.
Can PV power my heat pumps in winter?
Partly. Winter PV output is much lower than summer output, so buildings usually rely on the grid in winter and export in summer.
For feasibility and design, see our solar systems service.
Key takeaways
- Solar thermal suits steady hot water loads and daytime ventilation preheat.
- PV paired with heat pumps is the most common solar strategy for electrified buildings.
- Seasonal mismatch between solar supply and heating demand shapes every design.
- Interconnection, net metering and electrical code requirements vary by province and utility.
- Monitor solar output so failures do not go unnoticed behind backup systems.
Talk to an engineer
Have a project or a problem this guide touches on? Tell us about the building and we’ll be in touch within one hour.