Duct leakage is invisible once the ceiling is closed, but it costs energy every hour the fan runs. Leaky supply ducts deliver less air to the spaces they serve, forcing fans to work harder. Leaky return or exhaust ducts can draw air from unwanted places. In critical facilities, leakage can compromise pressure relationships and contamination control.
The Sheet Metal and Air Conditioning Contractors' National Association (SMACNA) publishes the standards most often used in North America to specify duct sealing and test leakage. This guide explains seal classes, leakage classes and how they fit together in a specification.
The two key SMACNA documents
- SMACNA HVAC Duct Construction Standards: Metal and Flexible defines duct construction by pressure class and sets out seal classes, describing which joints and seams must be sealed.
- SMACNA HVAC Air Duct Leakage Test Manual defines leakage classes and the method for testing ductwork for leakage.
Recent editions of the Duct Construction Standards call for all ducts to be sealed to Seal Class A by default, regardless of pressure class, a change from older editions in which lower-pressure ducts could have lower seal classes. Specifications still often reference seal classes, so it is worth understanding them. Confirm which edition is cited in the project specification.
Seal classes
Seal classes describe what must be sealed.
| Seal class | What must be sealed |
|---|---|
| Class A | All transverse joints, longitudinal seams and duct wall penetrations |
| Class B | All transverse joints and longitudinal seams |
| Class C | Transverse joints only |
Transverse joints connect sections of duct; longitudinal seams run along the length of each section. Wall penetrations include rods, screws, pipes and fittings passing through the duct wall.
Sealing is done with mastics, gaskets, approved tapes, or a combination. Products must be compatible with the duct material and pressure, and must meet flame spread and smoke developed requirements under CAN/ULC-S102 where required by the NBC or provincial code.
Pressure classes
SMACNA duct construction is organized by static pressure class, ranging from low pressure classes of 125 Pa (0.5 in. w.c.) up to high pressure classes of 2500 Pa (10 in. w.c.), with separate positive and negative ratings. The designer assigns a pressure class to each section of ductwork based on the expected operating pressure. Higher pressure classes require heavier gauge, closer reinforcement and stronger joints.
A common error is to assign a single low pressure class to all ductwork, even sections close to the fan that see much higher pressures. Medium and high pressure supply ducts upstream of VAV boxes should be classed and tested accordingly.
Leakage classes and the leakage factor
Leakage class describes how much leakage is allowable. SMACNA expresses allowable leakage with the equation:
F = CL x P^0.65
where F is the leakage rate per unit of duct surface area, CL is the leakage class, and P is the test pressure. In imperial units, F is in cfm per 100 square feet of duct surface and P is in inches of water. SI versions of the test manual express F in L/s per square metre and P in pascals, with correspondingly converted CL values.
A lower CL means tighter ductwork. Commonly specified leakage classes in imperial terms include:
| Leakage class (CL, imperial) | Typical application |
|---|---|
| 3 or lower | Round duct sealed to Seal Class A; tight systems such as laboratories, healthcare and cleanrooms |
| About 6 | Rectangular duct sealed to Seal Class A, typical commercial work |
| Much higher | Unsealed or poorly sealed ductwork |
The leakage manual provides expected leakage classes for different duct types (round, flat oval, rectangular) when sealed to each seal class. Round duct with sealed joints is typically tighter than rectangular because it has fewer seams and joints per unit area.
Why it matters
Energy
Leakage forces the fan to move more air to deliver the same airflow at outlets. Since fan power rises with both airflow and pressure, even modest leakage percentages can noticeably increase fan energy, particularly in high-pressure supply ducts that run long hours. Leakage outside the conditioned envelope, such as in unconditioned attics or shafts open to the exterior, also wastes heating and cooling energy.
Airflow and comfort
Leaks upstream of terminal units reduce available pressure at the far end of the system. Spaces at the ends of runs are the first to suffer.
Critical spaces
In healthcare, laboratories and cleanrooms, leakage can undermine pressure cascades and allow contaminated air to escape exhaust systems. CSA Z317.2 and laboratory guidance place a high priority on tight ductwork for these applications. Exhaust ducts serving hazardous fumes should be designed for minimal leakage and, where possible, kept under negative pressure inside the building.
Energy code requirements
NECB 2020 includes requirements for duct sealing and, for higher-pressure ductwork, leakage testing of a portion of the system. ASHRAE 90.1 has comparable provisions. Exact pressure thresholds, the portion of ductwork to be tested and the allowable leakage class vary by edition and by provincial adoption. Confirm the requirements that apply to the project with the authority having jurisdiction and the energy compliance path being used. See NECB 2020 and HVAC compliance.
Writing a duct sealing and testing specification
A clear specification typically includes:
- The SMACNA standards and editions referenced.
- Pressure class for each duct section, shown on drawings or schedules.
- Seal class (normally Class A for all ducts).
- Allowable leakage class by system or pressure class.
- Which sections must be tested and at what test pressure.
- Test procedure per the SMACNA Air Duct Leakage Test Manual.
- Who performs and witnesses tests, and the reporting format.
- Requirement to retest after repairs until results pass.
- Testing before insulation and concealment.
Testing before insulation and ceilings is critical. Once ducts are wrapped and concealed, finding and fixing leaks is costly and disruptive.
How testing works in brief
A section of ductwork is isolated by capping open ends, then pressurized with a calibrated test rig consisting of a fan, a flow measuring device and a manometer. The flow required to hold the test pressure equals the leakage. That leakage is compared against the allowable value calculated from the leakage class, duct surface area and test pressure. Details are covered in our guide to duct leakage testing procedures.
Frequently asked questions
Does sealing all ducts to Seal Class A guarantee low leakage?
No. Seal class describes what must be sealed, not how well. Workmanship, sealant quality and joint type all matter. Testing is the only way to confirm actual leakage.
How much of the ductwork should be tested?
It depends on the code and project. Energy codes often require a percentage of high-pressure ductwork. Critical facilities often test all of it. Owners can specify more testing than the code minimum.
Key takeaways
- Seal classes define what must be sealed; current SMACNA practice calls for Seal Class A on all ducts.
- Leakage classes define allowable leakage using F = CL x P^0.65.
- Assign pressure classes to each duct section based on actual operating pressure.
- Test before insulation and concealment, and retest after repairs.
- Tight ductwork saves fan energy, improves airflow delivery and protects critical spaces. Independent duct leakage testing provides documented proof.