In a Canadian winter, outdoor air holds very little moisture. Air at -20°C (-4°F) and saturated contains well under 1 gram of water per kilogram of dry air. When that air is brought inside and heated to 21°C (70°F), its relative humidity can fall to 10 percent or less. Occupants notice dry skin, irritated eyes and static shocks; wood finishes, musical instruments, artwork and some processes are affected too.
Humidification adds moisture back. It also adds risk: moisture that reaches cold parts of the building envelope can condense, causing frost, water damage and mould. Good humidification design in cold climates is as much about limiting humidity as adding it.
Which buildings need humidification?
Many ordinary commercial buildings in Canada operate without active humidification. Comfort standards such as ASHRAE 55 do not set a lower humidity limit for thermal comfort, although very dry conditions can cause discomfort and static electricity. Humidification is typically justified for:
| Building or space | Typical reason |
|---|---|
| Hospitals and healthcare | CSA Z317.2 and ASHRAE 170 set humidity ranges for many spaces, such as operating rooms |
| Museums, galleries, archives | Protection of collections from dimensional change and cracking |
| Laboratories and cleanrooms | Process requirements and static control |
| Printing, textile and wood products | Material stability and static control |
| Electronics manufacturing | Electrostatic discharge control |
| Data centres | Generally not required for modern IT equipment; some facilities still maintain a minimum dew point |
| Offices and schools | Optional, for comfort; must be weighed against envelope risk |
Where humidity is optional, a modest winter target is often a reasonable balance. Where it is required, the building envelope must be designed or verified to handle it.
The envelope limit
When warm, humid indoor air reaches a surface colder than its dew point, moisture condenses. In winter, the coldest interior surfaces are usually window glass, window frames, thermal bridges at slab edges and steel framing, and any place where indoor air leaks into the wall or roof assembly.
Two moisture paths matter:
- Surface condensation on windows and cold interior surfaces, which is visible and often the first sign of trouble.
- Interstitial condensation, where indoor air leaks through gaps in the air barrier into walls and roofs and condenses or freezes on cold layers. This is hidden and more damaging.
As outdoor temperature falls, the maximum indoor humidity the envelope can tolerate falls too. In the coldest weather, buildings with ordinary double glazing and aluminum frames may only tolerate indoor relative humidity in the range of roughly 20 to 30 percent without condensation, depending on glazing, frames and air movement. High-performance envelopes tolerate more.
Practical steps
- Reset humidity setpoint with outdoor temperature. Lower the indoor humidity target as it gets colder, so that the indoor dew point stays below the coldest surface temperatures.
- Check the envelope. Infrared thermography during cold weather reveals thermal bridges and air leaks that will limit humidification.
- Keep the building slightly positive or neutral with care. Positive pressure pushes humid indoor air into the envelope. Buildings with high humidity targets need especially good air barriers.
- Model critical assemblies where high humidity is required, such as museums and pools, using hygrothermal analysis.
Our guide on condensation and mould prevention covers envelope interaction in more detail.
Humidifier types
Humidifiers fall into two broad families: isothermal (steam) and adiabatic (evaporative or atomizing).
Steam humidifiers
Steam humidifiers add water vapour directly to the airstream. Because steam is already vapour, it does not cool the air.
- Electrode humidifiers pass current through water to boil it. Simple, but performance depends on water conductivity, and cylinders need periodic replacement.
- Resistive element humidifiers use heating elements. They work with demineralized or reverse osmosis water for low maintenance.
- Gas-fired steam generators use natural gas to boil water, reducing electrical demand and often operating cost where gas is cheap.
- Direct injection from a central boiler uses building steam. This requires attention to boiler water treatment chemicals, which may not be acceptable in occupied air, particularly in healthcare.
- Steam-to-steam generators use boiler steam to make clean steam from treated water, avoiding chemical carryover.
Adiabatic humidifiers
Adiabatic humidifiers evaporate liquid water into the air. The energy to evaporate the water comes from the air itself, which cools it.
- Evaporative media humidifiers pass air through wetted media.
- High-pressure atomizing systems spray fine water droplets through nozzles.
- Ultrasonic humidifiers create a fine mist using high-frequency vibration.
- Compressed air atomizing systems use air and water nozzles.
Adiabatic systems use much less electricity at the humidifier, but the cooling effect must be made up with heating. In winter, a building may use economizer free cooling at the same time, so the cooling effect can be useful in buildings with internal heat gains.
Comparison
| Factor | Steam | Adiabatic |
|---|---|---|
| Energy at the humidifier | High: roughly 0.7 kWh or more per kg of water | Low |
| Effect on air temperature | Little or none | Cools air, requiring reheat or offsetting internal gains |
| Water quality needs | Varies by type; RO or DI water reduces maintenance | RO or DI water usually essential to avoid mineral dust and fouling |
| Hygiene risk | Low, since water is boiled | Requires careful water management to control bacterial growth |
| Absorption distance | Short to moderate, depending on dispersion design | Can be longer; droplets must evaporate before downstream components |
| Typical use | Healthcare, labs, smaller systems | Large air handlers, data centres, buildings with economizer operation |
Design details that matter
- Absorption distance. Steam or mist must be fully absorbed before reaching coils, filters, dampers, fans or duct elbows. Wet downstream components lead to corrosion and microbial growth. Manufacturers publish absorption distances based on airflow, temperature and dispersion design.
- Location. Place humidifiers where the air is warm enough to absorb moisture, typically after the heating coil. Avoid locations where air is near saturation.
- High-limit control. A duct high-limit humidity sensor downstream prevents over-saturation when airflow drops or controls fail.
- Airflow proving. Interlock humidifiers with fan operation so they do not run without airflow.
- Drainage. Provide drain pans and drains under humidifier sections, and slope ducts where condensation could occur.
- Water treatment. Use the water quality the manufacturer specifies. Mineral deposits reduce output and, for adiabatic types, can release fine mineral dust into the air.
- Hygiene. Adiabatic systems must avoid stagnant water. Follow manufacturer guidance on flushing, draining and cleaning, and include them in the building's water management plan.
Controls
A typical control approach uses a space or return humidity sensor to modulate humidifier output, with a supply duct high-limit sensor overriding it. In cold climates, add an outdoor temperature reset of the humidity setpoint. Accurate humidity sensors are essential; they drift over time and need periodic calibration against a reference instrument.
Frequently asked questions
Will humidification reduce static shocks?
Generally yes. Static electricity builds up more easily in very dry air. Even a modest increase in humidity reduces static, although floor and footwear materials also matter.
Why are my windows wet when the humidifier runs?
The indoor dew point is above the glass surface temperature. Lower the humidity setpoint, especially in very cold weather, or improve window performance and air movement across the glass.
Is steam from the main building boiler acceptable for humidification?
It depends on boiler water treatment and the space use. Many facilities, especially healthcare, use clean steam generators or dedicated humidifiers to keep treatment chemicals out of the air.
Key takeaways
- Outdoor air in Canadian winters is extremely dry, and heated indoor air can drop to very low relative humidity.
- Humidify where codes, standards or processes require it; for comfort, weigh the benefit against envelope risk.
- Reset humidity setpoints downward as outdoor temperature falls to prevent condensation on and inside the envelope.
- Steam humidifiers are hygienic but energy intensive; adiabatic humidifiers use less energy but need excellent water treatment and hygiene.
- Respect absorption distances, provide high-limit control, and verify the envelope before raising winter humidity.
Talk to an engineer
Have a project or a problem this guide touches on? Tell us about the building and we’ll be in touch within one hour.